Modelling Transformers from data sheets or factory test certificates
조회 수: 7 (최근 30일)
이전 댓글 표시
I have data from 2 similar 33/11kv transformers
Tx1:
Positive Sequence resistance/reactance + Zero Sequence resistance/reactance (all per unit)
Tx2:
Primary and secondary winding resistance (ohms), no load losses (watts and amps), impedance/reactance at full load (%)
How do these figures get intergrated into a simscape electrical 3 lim transformer?
댓글 수: 0
답변 (1개)
Joel Van Sickel
2020년 8월 4일
이동: Sabin
2022년 12월 19일
Hello Joshua,
You primarily need the per unit resistance and inductance of the two windings. You would need to convert the tx2 data on impedance/reactance at full load to per unit as well. Those would be enough to parameterize a linear transformer that gives you decent results at full load. You could then use the additional knowledge of no load losses to better tune the magnetization resistance to provide something more realistic.
Here is an example specificly for this type of transformer.
Please see it's doc page for specifics and if you are intersted, this the reference used for builiding this model: [1] IEC. International Standard IEC 60076-1, Power Transformer - Part 1: General, Edition 2.1, 2000–04. "Annex D: Three-phase transformer connections." 2000.
Regards,
Joel
댓글 수: 0
참고 항목
카테고리
Help Center 및 File Exchange에서 Simscape Electrical에 대해 자세히 알아보기
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!