Orifice (2P) Parametrization and Control
이전 댓글 표시
Modeling option: Vapor operating condition
Orifice type: Variable
Opening characteristic: Linear
Problem: I do not know how to reconcile the concepts of physical signal S, control member travel, maximum orifice area, in order to understand the actual fraction of orifice area that is open given a value for S.
Questions:
- Is S a physical signal between 0 and 1, no units (unit = 1)?
- Is S = 0 associated with control member position at closed orifice and S = 1 to the fully open orifice?
- Is the orifice assumed of "rectangular" cross section, thus orifice width = maximum orifice area / (control member travel + control member position at closed orifice)?
댓글 수: 1
Walter Roberson
2025년 3월 14일
답변 (1개)
Yifeng Tang
2025년 3월 19일
0 개 추천
Hi @Rinaldo
Is S a physical signal between 0 and 1, no units (unit = 1)?
S is a position input, with a length unit (m, cm, mm, inch, etc.). Together with the travel between open and close, this S value defines an opening fraction of the maximum opening area or max nominal flowrate.
Is S = 0 associated with control member position at closed orifice and S = 1 to the fully open orifice?
That'll depend on the values in the highlighted boxes below. You may define where “closed” is and which direction of S changes will open the orifice. Again, it's usually not 0 and 1. The actual extreme values depends on the control member travel parameter.

Is the orifice assumed of "rectangular" cross section, thus orifice width = maximum orifice area / (control member travel + control member position at closed orifice)?
I don't think there is a "width" here. You may view it as a mapping between the control member (spool?) position to the orifice area.
Hope this helps.
Yifeng