In the BLDC motor block, a non-standard d'q' Transformation is used. Does this affect the values of L_d and L_q?
조회 수: 43 (최근 30일)
이전 댓글 표시
Hi all,
I am looking to simulate a BDLC motor using the BLDC block included in the Motor Control Blockset.
As is described in the documentation for the block (https://www.mathworks.com/help/mcb/ref/bldc.html), a different d'q'-Transformation is used to model the BLDC instead of the standard dq-Transformation. Most importantly for my issue, the voltage is calculated by
instead of how it is calculated during standard dq-Transformation:
.
I am curious about the additional scaling factor of π. Why is it used during transformation?
Also, is the value of affected by this? More specifically, if i know the value of and in standard dq-coordinates, can i input these directly into the BLDC motor block or do i need to account for the different d'q'-coordinates first?
Best Regards
댓글 수: 0
채택된 답변
Shivam Gothi
2024년 11월 5일 11:06
I understand that the factor of “pi” is not as per the intended equation. To investigate, I analysed the subsystem blocks found inside the “BLDC” by selecting the block and then pressing “Ctrl+U”. To the best of my knowledge, I found that the equations coded inside the Simulink block are:
Upon reviewing, the factor of “pi” is indeed not included in the actual implementation, and it seems to be a typing mistake in the documentation. I also tried to run the BLDC control example and found it to be working satisfactorily.
Therefore, the equations are correctly implemented as pointed out by you. The factor of “pi” is a documentation error.
I hope this clarifies the situation !