Simulink Load Flow Analysis for Electric Fleet Charging Station

Dear Community, I am trying to perform PowerGUI Loadflow analysis for EV Charging station. The model converges but the load flow vaues on the DC bus is zero. Whether power_loadflow supports DC load Flow.

Can someone help me by providing guidance on how to preform the same Regards Vara

댓글 수: 1

Good day, did you made the GUI for the EV charging station? i really want to learn about it. Could you help me please?

댓글을 달려면 로그인하십시오.

답변 (1개)

Joel Van Sickel
Joel Van Sickel 2024년 1월 3일

0 개 추천

Load flow for this tool was designed specifically for AC systems. While it does support single phase and unbalanced lines, this does not include DC lines or sources. There are ways to represent DC systems as behavioral AC systems like here: https://www.mathworks.com/help/sps/ug/24-hour-simulation-of-a-vehicle-to-grid-v2g-system.html
specifically look at the V2G system.