Issue on Unbalanced Load Flow on Simscape Power System

조회 수: 5 (최근 30일)
Everytime that I try to calculate a tri phase load flow on a model that contains a synchronous machine, i get this error on Matlab Command Window: ‘Matrix close to singular or badly scaled’
However, the Balanced Load Flow works perfectly, for the same model.
Any idea how to solve this?
  댓글 수: 2
Joel Van Sickel
Joel Van Sickel 2020년 8월 17일
When you say tri phase load flow, do you mean load flow on an unbalanced system? Which load flow tool are you using and can you share your model?
Augusto Janssen Harger da Silva
Augusto Janssen Harger da Silva 2020년 8월 19일
Ops, sorry, I mistyped... Three phase load flow would be the correct expression. That means I am selecting the parameter "Connectors" to ABC instead of Single in Load Flow Bus Block.
I am using the load flow tool from the powergui block.

댓글을 달려면 로그인하십시오.

채택된 답변

Joel Van Sickel
Joel Van Sickel 2020년 8월 24일
Hello Augusto,
the issue is likely with the model. It is possible that your model is 'stiff' making it hard to simulate. You could try adding snubber resistors to your motor.
Here is an file with the model above set up for unbalanced load flow working in 2020a. If you have an older verison you can modify the example to switch it to unbalanced and see it working with a synchronous machine.
Regards,
Joel
  댓글 수: 2
Joel Van Sickel
Joel Van Sickel 2020년 8월 24일
편집: Joel Van Sickel 2020년 8월 24일
ignore that comment, change your angle values to this: [0 -120 120]
Augusto Janssen Harger da Silva
Augusto Janssen Harger da Silva 2020년 8월 27일
Thank you Joel, changing the angle values worked!