Voltage measurement problem with isolated system ?

조회 수: 64 (최근 30일)
Nicolo Blini
Nicolo Blini 2018년 6월 5일
답변: Joel Van Sickel 2024년 6월 10일
Hi everyone.
I have some problems with this simulation. I try to explain: my load is an electric arc furnace and each "controlled voltage source" is the arc voltage. There is a non-grounded star point.
Externally, I have to measure the three phase-to-ground voltages of each arc for control system. (those three voltage measurement blocks) referred to ground.
When I start the simulation I have this problem:
"The Voltage Measurement block 'Voltage Measurement2' is connected between two isolated networks. For a valid measurement, the positive and negative terminals of the block must be connected to electrical nodes that are part of the same electrical circuit. Also check if the ground reference node is defined for that circuit."
I could solve the problem putting a grounded star point load, but it's not the reality. Furthermore, I can't change the secondary winding of MT/BT transformer to Yg because it is delta in reality.
Some ideas? What can I do ?
Thanks.
  댓글 수: 3
Muhd Haziq
Muhd Haziq 2023년 7월 3일
how to solve this ?
Luke McDevitt
Luke McDevitt 2023년 11월 10일
I still have this same problem

댓글을 달려면 로그인하십시오.

답변 (2개)

Saad Ullah Khan
Saad Ullah Khan 2021년 2월 16일
Add a large resistance in parallel for each phase.

Joel Van Sickel
Joel Van Sickel 2024년 6월 10일
You would never measure the voltage from a floating source to ground, so there is something wrong in your approach. You can either measure the line to line voltage, and convert it to phase voltage, or ground the system.