I am having an issue using the 4-way valve Model Parameterization "By pressure-flow characteristic.
I am getting the error.
"Cannot find error message associated with 'sh:orifice_variable:VectorSize'."
My inputs are:
Tabulated Valve Openings [.20 .40 .60 .80 1]
Tabulated Pressure Differentials [2.5 5 10]
Tabulated Flow Rates [0 0 0; 5 10 20; 15 30 60; 40 80 160; 90 180 360;]
I am usinging R2011b
Thank you
댓글 수: 0
답변 (2개)
Guy Rouleau
2012년 2월 3일
0 개 추천
I am able to reproduce. This is definitely unexpected.
Please contact technical support with your model to report this problem and see if there is a workaround.
댓글 수: 0
Guy Rouleau
2012년 2월 3일
0 개 추천
The block should provide a clear error message explaining that the pressure-flow characteristic should have at least 4 values in each dimension.
Consequently, adding one more point to the "Tabulated Pressure Differentials" and one column to "Tabulated Flow Rates" should help.