Modbus RTU Write Simulink Block error
이전 댓글 표시
Hi community,
I am starting with the setup of a modbus RTU communication between my matlab simulink model and some surrounding devices. Using the new simulink block "modbus client read", I can read the register of my external device, which shows me, that I've created a stable communication. However, if I want to write a register on the device, using the block "modbus client write", I get the following error:
Error:An error occurred during simulation and the simulation was terminated
Caused by:
MATLAB System block 'untitled/Modbus Client Write/internalModbus' error occurred when invoking 'stepImpl' method of 'icomm.system.ModbusWrite'. The error was thrown from '
'C:\Program Files\MATLAB\R2024b\toolbox\icomm\modbus\modbus\modbusblks\+icomm\+system\ModbusWrite.p' at line 0'.
The Modbus server returned an invalid address error. Address + number of values to write is out of range.
The config of the write-block is pictured:

As aforementioned, it's the same connection as used for the reading process. The model is quite simple and broken down to the minimum, but I get the error anyway:

Now I am struggling how to proceed with this error. Maybe someone can help me out!
Best
Marco
답변 (1개)
Hi Marco,
I faced a similar issue in MATLAB R2024b.
The issue was with the input data type of the signal going into "Modbus Client Write" block which has to be "double" otherwise it will result in an error.
As seen in the following documentation as well, the "Data type" for the "Reg_x" input to the "Modbus Client Write" should be a "double":
Hope this resolves your issue.