I am generating code from my model using Simulink PLC Coder. However, even after setting:
>> set_param('<modelName>','DefaultParameterBehavior','Inlined')
certain built-in Simulink blocks appear as separate function blocks in the generated code with respect to the main code. How can I fully inline these blocks?

 채택된 답변

MathWorks Support Team
MathWorks Support Team 2023년 5월 9일

0 개 추천

The most likely cause of this is the "Data Type Conversion" block, which converts floating point values to integer values. If this could be the cause, implement the following workaround:
1. Open each "Data Type Conversion" block’s block parameters and set "Integer rounding mode" to "Simplest", as shown below:
 
2. Generate code, which should then not contain the this function.
Note that PLC Coder currently does not inline the generated code for internal library functions, as such functions may have several copies and in-lining would cause code size bloat.

추가 답변 (0개)