Pump system Thermal Liquid Modeling for Liquid Cooling

조회 수: 6 (최근 30일)
Jan Haustein
Jan Haustein 2022년 1월 17일
답변: Yifeng Tang 2023년 2월 1일
I am currently on a Liquid Cooling system and i wanted to know if the Model for the Pump is appropiate this way. I want to control the the flowrate later on in comparission to the temperture in the system. Please let me know if this model is right or what to change to make it better.

답변 (1개)

Yifeng Tang
Yifeng Tang 2023년 2월 1일
I noticed that the sensors in the model appear to be placed incorrectly.
For through variable (flowrate, current, heat flux) sensors, it needs to be in series of the flow, i.e. the fluid flow through the block (A to B or B to A; both OK but opposite sign).
For across variable sensors, it always measures a difference, so you need a reference point or place the sensor over two different nodes to measure (pressure, voltage, temperature) differences.
Check out this example on how the sensors should be placed:
Go into the subsystem labeled "S" and look for the sensors.