TuningGoal.WeightedVariance class
Package: TuningGoal
Frequency-weighted H2 norm constraint for control system tuning
Description
Use TuningGoal.WeightedVariance
to limit the
weighted H2 norm of the
transfer function from specified inputs to outputs. The H2 norm
measures:
The total energy of the impulse response, for deterministic inputs to the transfer function.
The square root of the output variance for a unit-variance white-noise input, for stochastic inputs to the transfer function. Equivalently, the H2 norm measures the root-mean-square of the output for such input.
You can use TuningGoal.WeightedVariance
for
control system tuning with tuning commands, such as systune
or looptune
.
By specifying this tuning goal, you can tune the system response to
stochastic inputs with a nonuniform spectrum such as colored noise
or wind gusts. You can also use TuningGoal.WeightedVariance
to
specify LQG-like performance objectives.
After you create a tuning goal object, you can configure it further by setting Properties of the object.
Construction
creates
a tuning goal Req
=
TuningGoal.Variance(inputname
,outputname
,WL,WR
)Req
. This tuning goal specifies that
the closed-loop transfer function H(s)
from the specified input to output meets the requirement:
||WL(s)H(s)WR(s)||2 < 1.
When you are tuning a discrete-time system, Req
imposes
the following constraint:
The H2 norm is scaled by the square root of the sample time Ts to ensure consistent results with tuning in continuous time. To constrain the true discrete-time H2 norm, multiply either WL or WR by .
Input Arguments
|
Input signals for the tuning goal, specified as a character vector or, for multiple-input tuning goals, a cell array of character vectors.
For more information about analysis points in control system models, see Mark Signals of Interest for Control System Analysis and Design. |
|
Output signals for the tuning goal, specified as a character vector or, for multiple-output tuning goals, a cell array of character vectors.
For more information about analysis points in control system models, see Mark Signals of Interest for Control System Analysis and Design. |
|
Frequency-weighting functions, specified as scalars, matrices, or SISO or MIMO numeric LTI models. The functions ||WL(s)H(s)WR(s)||2 < 1. WL provides the weighting for
the output channels of H(s),
and WR provides the weighting for the input channels.
You can specify scalar weights or frequency-dependent weighting. To
specify a frequency-dependent weighting, use a numeric LTI model.
For example:
WL = tf(1,[1 0.01]); WR = 10; If you specify MIMO weighting functions, then If you are tuning in discrete time (that is, using a A value of |
Properties
|
Frequency-weighting function for the output channels of the
transfer function to constrain, specified as a scalar, a matrix, or
a SISO or MIMO numeric LTI model. The initial value of this property
is set by the |
|
Frequency-weighting function for the input channels of the transfer
function to constrain, specified as a scalar, a matrix, or a SISO
or MIMO numeric LTI model. The initial value of this property is set
by the |
|
Input signal names, specified as a cell array of character
vectors that identify the inputs of the transfer function that the
tuning goal constrains. The initial value of the |
|
Output signal names, specified as a cell array of character
vectors that identify the outputs of the transfer function that the
tuning goal constrains. The initial value of the |
|
Models to which the tuning goal applies, specified as a vector of indices. Use the Req.Models = 2:4; When Default: |
|
Feedback loops to open when evaluating the tuning goal, specified as a cell array of character vectors that identify loop-opening locations. The tuning goal is evaluated against the open-loop configuration created by opening feedback loops at the locations you identify. If you are using the tuning goal to tune a Simulink model
of a control system, then If you are using the tuning goal to tune a generalized state-space
( For example, if Default: |
|
Name of the tuning goal, specified as a character vector. For example, if Req.Name = 'LoopReq'; Default: |
Examples
Tips
When you use this tuning goal to tune a continuous-time control system,
systune
attempts to enforce zero feedthrough (D = 0) on the transfer that the tuning goal constrains. Zero feedthrough is imposed because the H2 norm, and therefore the value of the tuning goal (see Algorithms), is infinite for continuous-time systems with nonzero feedthrough.systune
enforces zero feedthrough by fixing to zero all tunable parameters that contribute to the feedthrough term.systune
returns an error when fixing these tunable parameters is insufficient to enforce zero feedthrough. In such cases, you must modify the tuning goal or the control structure, or manually fix some tunable parameters of your system to values that eliminate the feedthrough term.When the constrained transfer function has several tunable blocks in series, the software’s approach of zeroing all parameters that contribute to the overall feedthrough might be conservative. In that case, it is sufficient to zero the feedthrough term of one of the blocks. If you want to control which block has feedthrough fixed to zero, you can manually fix the feedthrough of the tuned block of your choice.
To fix parameters of tunable blocks to specified values, use the
Value
andFree
properties of the block parametrization. For example, consider a tuned state-space block:C = tunableSS('C',1,2,3);
To enforce zero feedthrough on this block, set its D matrix value to zero, and fix the parameter.
C.D.Value = 0; C.D.Free = false;
For more information on fixing parameter values, see the Control Design Block reference pages, such as
tunableSS
.This tuning goal imposes an implicit stability constraint on the weighted closed-loop transfer function from
Input
toOutput
, evaluated with loops opened at the points identified inOpenings
. The dynamics affected by this implicit constraint are the stabilized dynamics for this tuning goal. TheMinDecay
andMaxRadius
options ofsystuneOptions
control the bounds on these implicitly constrained dynamics. If the optimization fails to meet the default bounds, or if the default bounds conflict with other requirements, usesystuneOptions
to change these defaults.
Algorithms
When you tune a control system using a TuningGoal
,
the software converts the tuning goal into a normalized scalar value f(x). x is
the vector of free (tunable) parameters in the control system. The
software then adjusts the parameter values to minimize f(x)
or to drive f(x) below 1 if
the tuning goal is a hard constraint.
For TuningGoal.WeightedVariance
, f(x)
is given by:
T(s,x)
is the closed-loop transfer function from Input
to Output
. denotes
the H2 norm (see norm
).
For tuning discrete-time control systems, f(x) is given by:
Ts is the sample time of the discrete-time transfer function T(z,x).
Version History
Introduced in R2016aSee Also
systune
| looptune
| systune
(for slTuner)
(Simulink Control Design) | looptune (for slTuner)
(Simulink Control Design) | TuningGoal.Gain
| TuningGoal.LoopShape
| slTuner
(Simulink Control Design) | norm
| TuningGoal.Variance