Mapping Encoder channels to Physical DAQ ports- RTW & NI
조회 수: 4 (최근 30일)
이전 댓글 표시
I am trying to use a National Instruments PCIe-6323 DAQ and a NI BNC-2111 connector block with Real Time Windows Target and a quadrature encoder.
The BNC-2111 has physical ports PFI 7 and 12 but the PCIe-6323 encoder Counter 0 reads from PFI 8 and PFI 10. With Labview it is possible to redirect the channels so that say I can connect an cable to the PFI 7 port and it will act as my PFI 8 input for the encoder. I am trying to figure out how to do this within Matlab/Simulink/RTW.
I have read that this is possible but I can not seem to find any documentation.
댓글 수: 0
답변 (1개)
Jan Houska
2014년 5월 7일
Remapping of the encoder input channels is not supported with the Real-Time Windows Target driver. The driver always uses the default pin to signal mapping, as listed here:
CTR0 A (CTR0 SRC) : PFI8
CTR0 B (CTR0 AUX) : PFI10
CTR0 Z (CTR0 GATE) : PFI9
CTR1 A (CTR1 SRC) : PFI3
CTR1 B (CTR1 AUX) : PFI11
CTR1 Z (CTR1 GATE) : PFI4