How to measure torque and rpm of compressor in refrigeration cycle?

조회 수: 3 (최근 30일)
Aman
Aman 2024년 12월 4일
답변: Yifeng Tang 2024년 12월 13일
I am not getting that which blocks and how should i approach for measuring compressor power for which i need these 2 quantities?
I have attached the model on which I am working.

답변 (1개)

Yifeng Tang
Yifeng Tang 2024년 12월 13일
Use a Ideal Torque Sensor, connect it in series with the compressor R port, and now you are measuring the shaft torque. Multiply the torque by the angular velocity, you'll get the power. See picture below.
If you are using a motor block to drive the compressor, instead of an ideal angular velocity source, you won't have the angular velocity directly. In such case, connect an ideal rotational motion sensor in parallel to the compressor, you'll have a measured angular velocity that way.
Another way is to use a "Probe" block in Simscape to extract the power variable from the compressor directly as a Simulink signal.